Impact of Mechanical Deformations of Transformer Corners on Core Losses

Abstract : The clamping of the power transformer magnetic circuit allows maintaining the sheet stack and provides an additional mechanical rigidity. It has consequences on the acoustic noise of transformers as the magnetic cores of power transformers vibrate because of the magnetostriction and, if the corners are considered, Maxwell's forces. The indirect impact of a lack of clamping on the core losses is studied, especially on the interlaminar air gaps in the corners. In this paper, it is shown numerically with finite element modeling and experimentally with a specific testbench that induced vibrations can change the flux distribution and thus the losses.
Document type :
Journal articles
Complete list of metadata

https://hal-univ-artois.archives-ouvertes.fr/hal-03350801
Contributor : Guillaume Parent Connect in order to contact the contributor
Submitted on : Tuesday, May 17, 2022 - 9:20:36 AM
Last modification on : Wednesday, May 18, 2022 - 7:04:01 PM

File

2013_SMM_Proof_RP_GP_JPL_JFB_T...
Files produced by the author(s)

Identifiers

Collections

Citation

Remi Penin, Guillaume Parent, Jean-Philippe Lecointe, Jean-Francois Brudny, Thierry Belgrand. Impact of Mechanical Deformations of Transformer Corners on Core Losses. IEEE Transactions on Magnetics, Institute of Electrical and Electronics Engineers, 2015, 51 (4), pp.8400605. ⟨10.1109/TMAG.2014.2363057⟩. ⟨hal-03350801⟩